Overview: what a small critical‑loads backup does
A small solar+battery backup is normally set up to power a handful of critical circuits (for example: refrigerator, sump pump, router/modem, and a few lights/phone chargers) rather than the whole house; homeowners begin by listing the specific circuits and recording each device’s running watts and expected hours of operation during an outage[1]
Practical six‑step homeowner workflow
- Inventory critical loads and hours: list each device, its running watts, and how many hours you need it during the outage[1].
- Compute energy need (Wh): multiply each device’s running watts by hours to get watt‑hours, then sum those Wh values to get the total energy required for your target outage duration[1].
- Pick battery capacity by usable kWh: when a manufacturer publishes usable capacity, use that usable kWh to estimate runtime (example: Tesla lists 13.5 kWh usable for a single Powerwall)[2].
- Select an inverter sized for continuous and surge loads: choose an inverter whose published continuous rating covers your steady load and whose peak/surge rating covers motor starts (sump pumps and refrigerator compressors have high start currents)[4].
- Choose listed transfer equipment and wire per instructions: small systems that energize only a subpanel require an approved transfer method (manufacturer backup gateway, manual transfer switch, or ATS) and must be wired per the manufacturer’s guide and listing[3][10].
- Obtain permits and work with qualified installers: follow NEC/NFPA/UL and local AHJ requirements and use qualified/certified installers as manufacturers and standards bodies require[3][5][6][7].
Sizing: energy (Wh) vs capacity (kWh) vs runtime
Start with watts × hours → watt‑hours (Wh) for each device and sum to get the total outage energy requirement; EnergySage shows this arithmetic in its homeowner examples[1].
To estimate runtime from a marketed battery, use the manufacturer‑stated usable kWh rather than the nameplate or gross capacity; for example, Tesla documents a single Powerwall as 13.5 kWh usable[2].
Inverter selection: continuous rating, surge rating, and motor starts
Inverter selection must account for both continuous power need and motor starting (surge) currents; sump pumps and refrigerator compressors can draw several times their running current at start, so select an inverter whose published surge (peak) rating covers those starts[4].
Always read the inverter manufacturer’s datasheet for the exact continuous power, surge capability, and efficiencies for the model you plan to buy—manufacturer datasheets (for example, Victron’s MultiPlus‑II) publish these specs[4].
If the inverter’s surge capability is insufficient for motor starts, consider a higher‑surge inverter or motor‑start assist options documented by inverter manufacturers[4].
Wiring and transfer switching: how the backup supplies only the critical loads
Critical loads are commonly wired to a dedicated backup or critical‑loads subpanel so the battery/inverter supplies only that subpanel rather than the whole house; manufacturer installation manuals (for example Tesla’s Powerwall manual) document critical‑loads subpanel and transfer‑switch wiring patterns[3].
For homeowners who plan to install or modify a subpanel, see our step‑by‑step guidance on installing a subpanel safely for typical load calculation and grounding considerations here (this external how‑to covers practical subpanel topics that are naturally relevant when wiring a critical‑loads panel).
Approved transfer methods include manufacturer backup gateways, listed manual transfer switches, or automatic transfer switches; consult the manufacturer installation guide for wiring, labeling, and limitations (for example, Generac’s 100 A ATS guide shows load‑center/ATS wiring steps) and follow the guide exactly[10][3]
Codes, standards, and safety checklist
- UL listing: inverter and ESS products are typically required to be listed to applicable UL standards (for example UL 1741 and system standards such as UL 9540); UL publishes testing and certification guidance for advanced inverter/ESS behavior[7].
- Interconnection and anti‑islanding: IEEE 1547 describes the interconnection and anti‑islanding requirements that utilities and interconnection processes reference[12].
- NEC & local AHJ: NEC Articles 702/705/706 (and related guidance) govern optional standby, interconnected generation, and ESS wiring and identification; state/local AHJs adopt and interpret these provisions—see a practitioner summary from NCOSFM[5].
- Fire and siting: NFPA 855 is the national standard for fire‑safety, separation, and emergency response requirements for stationary ESS installations; local adoption varies, so check the AHJ[6].
Architectural choices: AC‑coupled vs DC‑coupled
AC‑coupled and DC‑coupled solar+battery architectures have different wiring, performance, and retrofit implications; EnergySage outlines the pros and cons of each approach and how they affect system layout and retrofits[11].
Costs and benchmarking
For consumer‑facing installed price examples, EnergySage reports that a 13.5 kWh battery‑size system is often quoted around ~$1,000–$1,200 per kWh installed, which translates to roughly $12,000–$16,000 installed for a 13.5 kWh system before incentives[1].
Research‑level reports from DOE/NREL provide different cost breakdowns and benchmarking useful for comparing component and soft costs if you want deeper industry context[8][9].
Installer qualifications and the final steps
Manufacturer installation manuals show wiring, commissioning, and installer qualification requirements; major manufacturers require qualified or certified installers and strict adherence to the manual[3].
Before commissioning: obtain permits, submit interconnection paperwork, use listed equipment for transfer switching, and have the installation inspected per local AHJ rules and the applicable NEC/NFPA/UL requirements[3][5][6][7].